Type: Three-phase, brushless, self-excited synchronous alternator with PMG excitation
-
Frequency: 50 / 60 Hz
-
Power Factor: 0.8
-
Voltage Range: 380/220V – 480/277V (reconnectable in star, delta, or parallel configurations)
-
Voltage Regulation: ±1.0%
-
Total Harmonic Distortion (THD): <5.0% (balanced load), <1.5% (no load)
-
Sustained Short Circuit Current: >300% rated current for 10 seconds
-
Efficiency: Up to 95.3% at full load
-
Overload Capacity: 110% for one hour in a six-hour cycle
-
Telephone Harmonic Factor (THF): <2%
-
Telephone Interference Factor (TIF): <50
-
Short Circuit Ratio (1/Xd): 0.09 typical
-
Reactances (Per Unit at Rated kVA):
-
Xd (Synchronous): 2.83–3.53
-
X’d (Transient): 0.12–0.17
-
X’’d (Subtransient): 0.09–0.12
-
Xq (Quadrature): 2.21–2.82
-
X’’q (Quadrature Subtransient): 0.24–0.34
-
X₂ (Negative Sequence): 0.16–0.23
-
X₀ (Zero Sequence): 0.06–0.10
-
Time Constants:
-
Waveform Distortion: <1.5% (no load), <5% (balanced linear load)
-
Sustained Short Circuit: 300% of rated current for 10 seconds
-
Insulation Class: H (125°C rise at 40°C ambient)
-
Protection: IP23 (optional IP44 with derating)
-
Cooling: Self-ventilated air cooling (1.035 m³/s @50Hz, 1.312 m³/s @60Hz)
-
Frame: Rigid steel structure with cast aluminum front and rear covers
-
Winding: Double-layer stator winding, 2/3 pitch design eliminates triple harmonics
-
Rotor: Damped rotor with dynamic balancing to BS6861 standards
-
Bearings:
-
Overspeed Capability: 120% of rated speed (2250 rpm)
-
Leads: 12 reconnectable leads for flexible configuration (star/delta/parallel star)
-
Inertia (WR²): 8.98 kg·m² (single bearing) / 8.70 kg·m² (double bearing)
-
Weight:
-
Rotor: 617 kg (single bearing) / 588 kg (double bearing)
-
Stator: 722 kg
-
Complete Alternator: 1543 kg (single bearing) / 1535 kg (double bearing)
-
Shipping Weight: 1635 kg (50Hz) / 1625 kg (60Hz)
-
Packing Dimensions: 166 × 87 × 124 cm
-
Excitation System: PMG excitation with brushless AVR control
-
AVR Model: MX341 (standard), optional SX460, SX440, AS440, MX321
-
Voltage Regulation Accuracy: ±1.0%
-
Parallel Operation: Supported with compatible AVR
-
Protection Features:
-
RFI Suppression: BS EN 61000-6-2, BS EN 61000-6-4, VDE 0875G/N compliant
-
Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359
-
Certification: ISO9001 Quality Management System