Alternateur A.R.K5FS

A.R.K5FS Alternateur Industriel Haute Efficacité à Excitation PMG

L’**A.R.K5FS** offre une excellente stabilité de tension (**±1 %**), une faible distorsion harmonique (**THD < 5 %**) et une grande robustesse mécanique. Équipé d’une **excitation PMG** et d’un **AVR MX341**, il est idéal pour les systèmes **industriels, télécom et standby** opérant en conditions difficiles.

Alternator Model

A.R.K5FS

50Hz (kVA)

625

60Hz (kVA)

713
Système d’excitationSELF EXCITED
A.V.R.MX341 WITH PMG
Régulation de tension à régime établi ± 1.0 %
Court-circuit prolongé >300% OF RATED CURRENT
Facteur de puissance nominal0.8

Electrical Performance

  • Type: Three-phase, brushless synchronous alternator with PMG excitation

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 380/220V – 480/277V (star, delta, or parallel star)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced load), <1.5% (no load)

  • Sustained Short Circuit Current: >300% rated current for 10 seconds

  • Efficiency: Up to 95.3%

  • Overload Capacity: 110% for one hour in a six-hour period

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Short Circuit Ratio (1/Xd): 0.09 typical

  • Waveform Distortion: <1.5% (no load), <5% (linear load)

  • Sustained Short Circuit: 300% rated current for 10 seconds

Reactances (Per Unit at Rated kVA)

  • Xd (Synchronous): 2.83–3.53

  • X’d (Transient): 0.12–0.17

  • X’’d (Subtransient): 0.09–0.12

  • Xq (Quadrature): 2.21–2.82

  • X’’q (Quadrature Subtransient): 0.24–0.34

  • X₂ (Negative Sequence): 0.16–0.23

  • X₀ (Zero Sequence): 0.06–0.10

  • Leakage Reactance (XL): 0.05–0.06

  • Transient Time Constant (T’d): 0.08 s

  • Subtransient Time Constant (T’’d): 0.012 s

  • Armature Time Constant (Ta): 0.019 s

  • Open Circuit Field Time Constant (T’do): 2.5 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with derating)

  • Cooling: Self-ventilated air cooling (1.035 m³/s @50Hz, 1.312 m³/s @60Hz)

  • Frame: Steel frame with cast aluminum front and rear covers

  • Stator: Double-layer winding, 2/3 pitch eliminates 3rd, 9th, 15th harmonics

  • Rotor: Damped rotor dynamically balanced per BS6861 standards

  • Bearings:

    • Drive End: 6220-2RS (sealed-for-life ball bearing)

    • Non-Drive End: 6314-2RS (sealed-for-life ball bearing)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads for versatile connections

  • Mechanical Balance: Half-key dynamic balance in double bearing structure

  • Cooling Air Requirement: 1.035 m³/s (50Hz), 1.312 m³/s (60Hz)

  • Stator Winding Resistance: 0.0043 Ω/phase (at 22°C, star connection)

  • Rotor Winding Resistance: 1.96 Ω (at 22°C)

Dimensions & Weight

  • Rotor Weight: 617 kg (single bearing) / 588 kg (double bearing)

  • Stator Weight: 722 kg

  • Complete Alternator Weight: 1543 kg (single bearing) / 1535 kg (double bearing)

  • Inertia (WR²): 8.98 kg·m² (single bearing) / 8.70 kg·m² (double bearing)

  • Shipping Weight: 1635 kg (50Hz) / 1625 kg (60Hz)

  • Packing Dimensions: 166 × 87 × 124 cm

Regulation & Control

  • Excitation System: PMG excitation with brushless AVR control

  • AVR Model: MX341 (standard), optional SX460, SX440, AS440, MX321

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported with compatible AVR

  • Protection Features:

    • Stator winding and bearing overheat protection

    • Anti-condensation heater (optional)

  • RFI Suppression: Complies with BS EN 61000-6-2, BS EN 61000-6-4, VDE 0875G/N

  • Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Noise & Vibration: Dynamically balanced per BS6861 standards

Performance Summary

  • Efficiency Range: 94.5–95.3%

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% of rated current

  • Applications: Prime power, standby, rental, telecom, mobile power, refrigeration, lighting tower, and railway generator systems

Datasheet

Produits associés