Alternateur A.R.K6B

A.R.K6B Alternateur Industriel Robuste à Excitation PMG

L’**A.R.K6B** est un alternateur synchrone triphasé sans balais doté d’une **excitation PMG** et d’un **AVR MX341**, assurant une tension stable et propre sous charges variables. Avec **classe H**, **IP23** et un rendement jusqu’à **94,2 %**, il est parfaitement adapté aux applications **industrielles, mobiles et de location**.

Alternator Model

A.R.K6B

50Hz (kVA)

750

60Hz (kVA)

885
Système d’excitation SELF EXCITED
A.V.R. MX341 WITH PMG
Régulation de tension à régime établi ± 1.0 %
Court-circuit prolongé>300% OF RATED CURRENT
Facteur de puissance nominal 0.8

Electrical Performance

  • Type: Three-phase, brushless synchronous alternator with PMG excitation

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 380/220V – 480/277V (reconnectable in star, delta, or parallel star)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced linear load), <1.5% (no load)

  • Sustained Short Circuit Current: >300% rated current for 10 seconds

  • Efficiency: 93.0%–94.2% (depending on load and frequency)

  • Overload Capacity: 110% for one hour in a six-hour cycle

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Short Circuit Ratio (1/Xd): 0.09 typical

  • Power Ratings (Winding 311):

    • 50 Hz: 651–855 kVA (93.6–94.2% efficiency range)

    • 60 Hz: 710–970 kVA (93.0–93.6% efficiency range)

  • Reactances (Per Unit at Rated kVA):

    • Xd (Synchronous): 2.42–3.12

    • X’d (Transient): 0.15–0.20

    • X’’d (Subtransient): 0.10–0.15

    • Xq (Quadrature): 2.60–2.94

    • X’’q (Quadrature Subtransient): 0.20–0.28

    • X₂ (Negative Sequence): 0.18–0.22

    • X₀ (Zero Sequence): 0.09

    • Leakage Reactance (XL): 0.03

  • Time Constants:

    • Transient (T’d): 0.106 s

    • Subtransient (T’’d): 0.013 s

    • Armature (Ta): 0.035 s

    • Open Circuit Field (T’do): 2.91 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with power reduction)

  • Cooling System: Self-ventilated air cooling

    • 50 Hz: 2.18 m³/s

    • 60 Hz: 2.63 m³/s

  • Frame: Rigid steel frame with cast aluminum front and rear covers

  • Winding: Double-layer stator winding with 2/3 pitch to eliminate 3rd, 9th, and 15th harmonics

  • Rotor: Damped rotor dynamically balanced per BS6861 standards

  • Bearings:

    • Drive End: 6319 (sealed-for-life ball bearing)

    • Non-Drive End: 6228 (sealed-for-life ball bearing)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads for star, delta, or parallel star configuration

  • Inertia (WR²): 16.24–16.78 kg·m²

  • Cooling Air Requirement: 2.18 m³/s @50Hz, 2.63 m³/s @60Hz

  • Stator Resistance: 0.0039 Ω/phase at 22°C (star connection)

  • Rotor Resistance: 1.6 Ω at 22°C

Dimensions & Weight

  • Wound Rotor Weight: 760–865 kg

  • Wound Stator Weight: 895–938 kg

  • Complete Generator Weight: 1985–2045 kg

  • Shipping Weight (Crated): 2023–2030 kg

  • Packing Dimensions: 183 × 92 × 140 cm

Regulation & Control

  • Excitation System: PMG excitation with brushless AVR

  • AVR Models: MX341 (standard), MX321, SX440, SX460, AS440 (optional)

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (AVR-dependent)

  • Protection Features:

    • Stator winding and bearing overheat protection

    • Anti-condensation heater (optional)

    • Low-speed voltage drop protection

  • RFI Suppression: Complies with BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N

  • Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Cooling Air Requirement: 2.18 m³/s (50Hz), 2.63 m³/s (60Hz)

  • Noise & Vibration: Dynamically balanced per BS6861 standards

Performance Summary

  • Efficiency Range: 93.0%–94.2% across rated loads

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% rated current

  • Applications: Prime power, standby, telecom, mobile power, refrigeration, rental, railway, and lighting tower systems

Datasheet