A.R.K224G Alternator – Brushless, High-Performance Alternator for Industrial and Standby Power

The A.R.K224G alternator, developed by Arken Power Solutions, is a three-phase brushless synchronous alternator designed for industrial, rental, and standby power applications. It features a self-excited excitation system with a high-efficiency AVR (SX460 standard, SX440 optional) providing ±1% voltage regulation, THD below 5%, and efficiency up to 91.3%. With Class H insulation, IP23 protection, and rigid steel construction, it ensures reliability, excellent cooling, and stable output even under dynamic load conditions. Fully compliant with IEC60034, BS5000, VDE0530, NEMA MG1-22, and ISO9001, this alternator is optimized for both prime and standby generator systems, offering durability and exceptional electrical performance.

Alternator Model

A.R.K224G

50Hz (kVA)

83

60Hz (kVA)

97.5
Control SystemSELF EXCITED
A.V.R.SELF EXCITED
Voltage Regulation ± 1.0 %
Sustained Short Circuit >300% OF RATED CURRENT
Rated Power Factor0.8

Electrical Performance

  • Type: Three-phase, brushless, self-excited synchronous alternator

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Rated Voltage Range: 190–480 V (configurable for star, delta, or parallel star)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced load), <1.5% (no-load)

  • Sustained Short Circuit Current: >300% of rated current for 10 seconds

  • Efficiency: Up to 91.3% (depending on voltage and load)

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Excitation System: Self-excited, AVR-controlled

  • AVR Models: SX460 (standard), SX440 / AS440 optional, MX341 / MX321 (PMG) optional

  • Short Circuit Ratio (1/Xd): 6.0 typical

Reactances (Per Unit, Saturated)

  • Xd (Synchronous): 1.78–2.66

  • X’d (Transient): 0.14–0.20

  • X’’d (Subtransient): 0.09–0.14

  • Xq (Quadrature): 0.82–1.22

  • X’’q (Quadrature Subtransient): 0.13–0.17

  • X₂ (Negative Sequence): 0.12–0.16

  • X₀ (Zero Sequence): 0.07–0.11

  • Leakage Reactance (XL): 0.05–0.08

  • Time Constants:

    • Transient (T’d): 0.03 s

    • Subtransient (T’’d): 0.008 s

    • Open Circuit Field (T’do): 0.75 s

    • Armature (Ta): 0.007 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with 5–10% derating)

  • Cooling: Self-ventilated air cooling

    • 50 Hz: 0.216 m³/s (458 cfm)

    • 60 Hz: 0.281 m³/s (595 cfm)

  • Frame: Rigid steel frame with cast aluminum front and rear covers

  • Stator: Double-layer winding with auxiliary winding, 2/3 pitch eliminates triple harmonics

  • Rotor: Damped cage rotor, dynamically balanced per BS6861 standards

  • Bearings:

    • Drive End: 6315-2RS (ISO, sealed-for-life)

    • Non-Drive End: 6310-2RS (ISO, sealed-for-life)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads (star, delta, or parallel star)

  • Stator Resistance: 0.055 Ω/phase (22°C, series star connection)

  • Rotor Resistance: 0.94 Ω (22°C)

  • Rotor Inertia (WR²): 0.7136 kg·m² (single bearing) / 0.6818 kg·m² (double bearing)

Dimensions & Weight

  • Wound Rotor Weight: 126.75 kg (single bearing) / 118.38 kg (double bearing)

  • Wound Stator Weight: 139 kg

  • Complete Alternator Weight: 383 kg (single bearing) / 400 kg (double bearing)

  • Shipping Weight: 404–420 kg (crated)

  • Packing Dimensions: 105 × 57 × 96 cm

Regulation & Control

  • Excitation: Self-excited, AVR-controlled

  • AVR Models: SX460 (standard), SX440 / AS440 / MX341 / MX321 optional

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (AVR-dependent)

  • RFI Suppression: BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N compliant

  • Standards Compliance: IEC60034, GB755, BS5000, VDE0530, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Cooling Air Requirement: 0.216–0.281 m³/s depending on frequency

  • Noise & Vibration: Balanced per BS6861 mechanical standards

Performance Summary

  • Efficiency Range: 90.8–91.3%

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% rated current

  • Applications: Prime power, standby, rental, telecom, mobile, lighting tower, refrigeration, and railway generator systems