Baudouin Diesel Generator ARK-B 1500 L5

ARK-B 1500 L5 Diesel Generator – Powerful and Efficient Energy for Industrial Needs

The ARK-B 1500 L5 diesel generator by Arken Power Solutions delivers 1350 kVA prime and 1500 kVA standby power, ensuring exceptional performance for demanding industrial operations. It is powered by the Baudouin 12M33G1500/5, a 12-cylinder, turbocharged, water-cooled diesel engine designed for durability, fuel efficiency, and stable power output.

Featuring a LINZ PRO40M D/4 alternator with 96.8% efficiency, ±1% voltage regulation, and <3% THD, it ensures reliable and clean energy supply. Built in compliance with ISO 8528 and ISO 3046 standards, the ARK-B 1500 L5 operates at 91.8 dBA, includes a corrosion-resistant canopy, and comes with a 2-year or 1000-hour warranty, making it a trusted choice for continuous and standby power applications.

Power Prime (kVA / kW)

1350 / 1080

Power Standby (kVA / kW)

1500 / 1200

Speed (r.p.m)

1500

Standard Voltage

400/230VAC

Power Factor(Cos Phi)

0.8
BrandBAUDOUIN
Power PRP [kW]1200
Model12M33G1500/5
N° of Cylinders / Valves12/48
Engine Type4
Displacement [lt]39.2
AspirationTurbocharge and Aftercooler System
Bore[mm] x Stroke[mm]150x185
Compression Ratio15:1
Air FilterHeavy Duty
Cooling MethodWater Cooled (water + %50 antifreeze)
Total Coolant Capacity (lt)303
Governor TypeElectronic
Electrical System24VDC
Battery Charger Current55
Oil Capacity [lt]155
Exhaust Gas Flow PRP [m3/min]277
Exhaust Gas Temp. [°C]≤550
Air Flow PRP [m3/min]97.3
Cooling Air Flow PRP [m3/min]2100
Starter Power (kW)10
Standard Battery Voltage [V]24VDC
Standard Battery Capacity4x150Ah
Standard Battery TypeMaintenance-Free Lead Acid
BrandLinz
ModelPRO40M D/4
Voltage400 /230 VAC
Number of Phase3
Power Factor0.8
Number of Poles4
Connection TypeStar
BearingSingle

ENGINE
Arken Jenerator provides industrial diesel engines that meet ISO 8528, ISO 3046 specifications; heavy duty type; oil, air or water-cooled depending on the requirements; low fuel consumption; with mechanical and/or electronical type of governor mounted on fuel pump to ensure precise speed adjustment and regulation; with oil, fuel and air filter system based on diesel type; oil and fuel designed for heavy operational conditions in order to make sure the unit lasts a long time with high performance; 4-stroke; direct injection with all the limit and level sensors required for diesel protection. The diesel engine is supplied with all the necessary equipment for safe operation. Only engines designed for standby are not included in the production portfolio.

ALTERNATOR
Arken Jenerator uses original European brand alternators for its gensets, that complies with all international certificates, IEC 60034-1, ISO8528-3, EN50511, BS4999-5000 VDE 0530, depending on their power and requirements. The alternators, that has high efficiency and high performance for all conditions, have all the quality certificates and comply with world standards.

COOLING SYSTEM
Arken Jenerator chooses its radiators from the original selection or from approved vendor list of its engine on boards for the purpose of usability, spare part availability, high performance and maximum efficiency. 55C remote type radiators are appliible.

FRAME
Arken Jenerator manufactures its own chassis based on international standards for all generator sets. The frames are designed and manufactured to provide high strength from the inside of the plate panel or profile to the vibration and stresses.

FUEL TANK
Arken Jenerator uses an in-chassis daily fuel tank in generator sets up to 800kVA. Larger power sets are supplied with an external stand-type fuel tank. Fuel tanks can be manufactured from plate steel or other suitable materials in accordance with the relevant standards. Arken fuel tanks mainly include:

  • Fuel fill point and cap
  • Tank vents
  • Fuel outlet valve
  • Fuel return connection
  • Tank drain plug
  • Sludge, etc. accumulation section
  • Transparent fuel level gauge
  • Floating level switch / Automatic Fill (Optional)

CANOPY
To provide sound isolation (ISO8528-10:1998) and to protect the generator from corrosive effects of external weather conditions, cabinets or containers are used depending on the size of the generator or the degree of sound intensity. Even low noise level is targeted principally, the cabins are designed in order to deliver stated power, in addition to the conditions set by ISO3046 and ISO8528, according to the tropical climate at 50C ambient temperatures, relative humidity of 30% at sea level is designed to deliver the declared power. Cabs come with a compact construction, low height, low sound level, easy access to the engine-alternator and control panel, lifting at two point, exhaust silencer stored in the cabin for safety and non-corrosion protection, and with ease of disassembly.

DOCUMENTATION
Maintenance and operation manual, Engine and alternator manuals, Controller booklet, Warranty sheet, Electrical diagram.

WARRANTY
The warranty period begins from the date of the invoice of the item and runs upto 1 Year or 1000 hours.

Datasheet