Alternateur A.R.K6E

A.R.K6E Alternateur Industriel Sans Balais à Excitation PMG

L’**A.R.K6E** d’Arken Power Solutions est un alternateur synchrone triphasé sans balais avec **excitation PMG** et **AVR MX341**, offrant une régulation de tension **±1 %**, un **THD < 5 %** et un rendement jusqu’à **95,6 %**. Conçu avec isolation **classe H**, protection **IP23** et roulements étanches, il est idéal pour les applications **industrielles, télécom, location et secours**.

Alternator Model

A.R.K6E

50Hz (kVA)

1030

60Hz (kVA)

1200
Système d’excitation SELF EXCITED
A.V.R.MX341 WITH PMG
Régulation de tension à régime établi ± 1.0 %
Court-circuit prolongé >300% OF RATED CURRENT
Facteur de puissance nominal0.8

Electrical Performance

  • Type: Three-phase, brushless, self-excited synchronous alternator with PMG excitation

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 380/220V – 480/277V (configurable in star, delta, or parallel star)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced linear load), <1.5% (no-load)

  • Sustained Short Circuit Current: >300% rated current for 10 seconds

  • Efficiency: 94.7–95.6% depending on load and frequency

  • Overload Capacity: 110% for one hour in a six-hour cycle

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Short Circuit Ratio (1/Xd): 0.09 typical

  • Power Ratings (Winding 311):

    • 50 Hz: 720–950 kVA (Efficiency 95.3–95.6%)

    • 60 Hz: 800–1120 kVA (Efficiency 94.7–95.4%)

  • Reactances (Per Unit at Rated kVA):

    • Xd (Synchronous): 2.73–3.49

    • X’d (Transient): 0.15–0.19

    • X’’d (Subtransient): 0.08–0.10

    • Xq (Quadrature): 1.74–3.25

    • X’’q (Quadrature Subtransient): 0.18–0.24

    • X₂ (Negative Sequence): 0.09–0.10

    • X₀ (Zero Sequence): 0.08–0.10

    • Leakage Reactance (XL): 0.02–0.03

  • Time Constants:

    • Transient (T’d): 0.046 s

    • Subtransient (T’’d): 0.025 s

    • Armature (Ta): 0.03–0.04 s

    • Open Circuit Field (T’do): 3.03 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with 5–10% power reduction)

  • Cooling: Self-ventilated air cooling

    • 50 Hz: 1.614 m³/s (3420 cfm)

    • 60 Hz: 1.961 m³/s (4156 cfm)

  • Frame: Rigid steel structure with cast aluminum front and rear covers

  • Stator: Double-layer winding, 2/3 pitch design to eliminate triple harmonics

  • Rotor: Damped rotor dynamically balanced to BS6861 standards

  • Bearings:

    • Drive End: 6224 (sealed-for-life ball bearing)

    • Non-Drive End: 6317 (sealed-for-life ball bearing)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads for star, delta, or parallel star configuration

  • Inertia (WR²): 22.38–22.92 kg·m²

  • Winding Resistance:

    • Stator: 0.002 Ω/phase (22°C, star connection)

    • Rotor: 2.09 Ω (22°C)

Dimensions & Weight

  • Rotor Weight: 916–962 kg

  • Stator Weight: 1120 kg

  • Complete Alternator Weight: 2279–2329 kg

  • Shipping Weight (Crated): 2300 kg

  • Packing Dimensions: 183 × 92 × 140 cm

Regulation & Control

  • Excitation System: PMG excitation with brushless AVR

  • AVR Models: MX341 (standard), optional SX440, SX460, AS440, MX321

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (AVR-dependent)

  • Protection Features:

    • Stator winding and bearing overheat protection

    • Anti-condensation heater (optional)

    • Low-speed voltage drop protection

  • RFI Suppression: Complies with BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N

  • Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Cooling Air Requirement: 1.614 m³/s (50Hz), 1.961 m³/s (60Hz)

  • Noise & Vibration: Balanced per BS6861 mechanical standards

Performance Summary

  • Efficiency Range: 94.7–95.6%

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% rated current

  • Applications: Prime power, standby, telecom, mobile, lighting tower, refrigeration, railway, and industrial generator systems

Datasheet