Alternateur A.R.K6G

A.R.K6G Alternateur Industriel Sans Balais à Excitation PMG

L’**A.R.K6G** est un alternateur triphasé sans balais équipé d’une **excitation PMG** et d’un **AVR MX341**, garantissant une régulation **±1 %**, un **THD < 5 %** et un rendement jusqu’à **95,3 %**. Sa construction robuste avec **classe H** et **IP23** le rend idéal pour les groupes électrogènes **industriels, mobiles, de location et standby**.

Alternator Model

A.R.K6G

50Hz (kVA)

1250

60Hz (kVA)

1386
Système d’excitationSELF EXCITED
A.V.R. MX341 WITH PMG
Régulation de tension à régime établi ± 1.0 %
Court-circuit prolongé >300% OF RATED CURRENT
Facteur de puissance nominal0.8

Electrical Performance

  • Type: Three-phase, brushless synchronous alternator with PMG excitation

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 380/220V – 480/277V (reconnectable in star, delta, or parallel star)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced load), <1.5% (no load)

  • Sustained Short Circuit Current: >300% rated current for 10 seconds

  • Efficiency: 94.8–95.3% depending on frequency and load

  • Overload Capacity: 110% for one hour in a six-hour period

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Short Circuit Ratio (1/Xd): 0.09 typical

  • Power Ratings (Winding 311):

    • 50 Hz: 832–1091 kVA (Efficiency 95.1–95.3%)

    • 60 Hz: 960–1386 kVA (Efficiency 94.8–95.2%)

  • Reactances (Per Unit at Rated kVA):

    • Xd (Synchronous): 2.16–2.33

    • X’d (Transient): 0.15–0.20

    • X’’d (Subtransient): 0.07–0.08

    • Xq (Quadrature): 1.70–1.93

    • X’’q (Quadrature Subtransient): 0.20–0.23

    • X₂ (Negative Sequence): 0.06–0.09

    • X₀ (Zero Sequence): 0.07–0.09

    • Leakage Reactance (XL): 0.02–0.03

  • Time Constants:

    • Transient (T’d): 0.115 s

    • Subtransient (T’’d): 0.015 s

    • Armature (Ta): 0.038 s

    • Open Circuit Field (T’do): 3.6 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with 5–10% derating)

  • Cooling: Self-ventilated air cooling

    • 50 Hz: 2.18 m³/s (4619 cfm)

    • 60 Hz: 2.63 m³/s (5573 cfm)

  • Frame: Steel structure with cast aluminum front and rear covers

  • Stator: Double-layer winding, 2/3 pitch eliminates 3rd, 9th, and 15th harmonics

  • Rotor: Damped rotor dynamically balanced per BS6861 standards

  • Bearings:

    • Drive End: 6319 (sealed-for-life ball bearing)

    • Non-Drive End: 6228 (sealed-for-life ball bearing)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads for star, delta, or parallel star configuration

  • Inertia (WR²): 28.75–29.27 kg·m²

  • Winding Resistance:

    • Stator: 0.0015 Ω/phase (22°C, star connection)

    • Rotor: 2.45 Ω (22°C)

Dimensions & Weight

  • Rotor Weight: 1129–1190 kg

  • Stator Weight: 1135–1386 kg

  • Complete Alternator Weight: 2658–3130 kg (depending on configuration)

  • Shipping Weight (Crated): 2840–3130 kg

  • Packing Dimensions: 194 × 105 × 154 cm

Regulation & Control

  • Excitation System: PMG excitation with brushless AVR

  • AVR Models: MX341 (standard), optional MX321, SX440, SX460, AS440

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (AVR-dependent)

  • Protection Features:

    • Stator winding and bearing overheat protection

    • Anti-condensation heater (optional)

    • Low-speed voltage drop protection

  • RFI Suppression: Complies with BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N

  • Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Cooling Air Requirement: 2.18 m³/s (50Hz), 2.63 m³/s (60Hz)

  • Noise & Vibration: Dynamically balanced per BS6861 mechanical standards

Performance Summary

  • Efficiency Range: 94.8–95.3%

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% rated current

  • Applications: Prime power, standby, rental, telecom, mobile, lighting tower, refrigeration, and railway generator systems

Datasheet