Alternator A.R.K184J

A.R.K184J Alternator – Brushless, High-Performance Alternator for Continuous and Standby Power

The A.R.K184J alternator, engineered by Arken Power Solutions, is a three-phase brushless synchronous alternator designed for superior performance in industrial, rental, and backup power applications. Featuring a self-excited excitation system regulated by SX460 AVR (with SX440 optional), it ensures ±1% voltage regulation, THD below 5%, and efficiency up to 87.8%. Built with Class H insulation, IP23 protection, and dynamically balanced rotors, it delivers clean, stable, and reliable power for a wide range of heavy-duty generator systems. Certified under IEC60034, BS5000, NEMA MG1-22, and ISO9001, the A.R.K184J is ideal for both prime and standby power operations in demanding environments.

Alternator Model

A.R.K184J

50Hz (kVA)

42.5

60Hz (kVA)

50
Control SystemSELF EXCITED
A.V.R. OPTIONAL SX440
Voltage Regulation ± 1.0 %
Sustained Short Circuit>300% OF RATED CURRENT
Rated Power Factor0.8

Electrical Performance

  • Type: Three-phase, brushless, self-excited synchronous alternator

  • Frequency: 50 / 60 Hz

  • Power Factor: 0.8

  • Voltage Range: 190–480 V (series star, parallel star, or delta configurations)

  • Voltage Regulation: ±1.0%

  • Total Harmonic Distortion (THD): <5% (balanced linear load), <1.5% (no-load)

  • Sustained Short Circuit Current: >300% of rated current

  • Efficiency: Up to 87.8% (depending on frequency and voltage)

  • Telephone Harmonic Factor (THF): <2%

  • Telephone Interference Factor (TIF): <50

  • Excitation System: Self-excited, AVR-controlled

  • AVR Models: SX460 (standard), SX440 optional

  • Short Circuit Ratio (1/Xd): 6.0 typical

Reactances (Per Unit, Saturated)

  • Xd (Synchronous): 1.793–2.431

  • X’d (Transient): 0.136–0.185

  • X’’d (Subtransient): 0.074–0.101

  • Xq (Quadrature): 0.866–1.174

  • X’’q (Quadrature Subtransient): 0.151–0.205

  • X₂ (Negative Sequence): 0.114–0.154

  • X₀ (Zero Sequence): 0.028–0.038

  • Leakage Reactance (XL): 0.056–0.076

  • Time Constants:

    • Transient (T’d): 0.025 s

    • Subtransient (T’’d): 0.016 s

    • Open Circuit Field (T’do): 0.59 s

    • Armature (Ta): 0.0105 s

Construction & Design

  • Insulation Class: H (125°C rise at 40°C ambient)

  • Protection: IP23 (optional IP44 with 5–10% derating)

  • Cooling: Self-ventilated air cooling

    • 50 Hz: 0.15 m³/s (318 cfm)

    • 60 Hz: 0.19 m³/s (403 cfm)

  • Frame: Steel structure with cast aluminum front and rear covers

  • Stator: Double-layer winding, 2/3 pitch eliminates triple harmonics

  • Rotor: Damped cage rotor, dynamically balanced to BS6861 standards

  • Bearings:

    • Drive End: 6309-2RS (ISO, sealed-for-life)

    • Non-Drive End: 6306-2RS (ISO, sealed-for-life)

  • Overspeed Capability: 120% of rated speed (2250 rpm)

  • Leads: 12 reconnectable leads (star, delta, or parallel star)

  • Stator Resistance: 0.214 Ω/phase (22°C, star connection)

  • Rotor Resistance: 0.93 Ω (22°C)

  • Rotor Inertia (WR²): 0.2978 kg·m² (single bearing) / 0.2921 kg·m² (double bearing)

Dimensions & Weight

  • Wound Rotor Weight: 77.15 kg (single bearing) / 73.95 kg (double bearing)

  • Stator Weight: 79 kg

  • Complete Alternator Weight: 226 kg (single bearing) / 214 kg (double bearing)

  • Shipping Weight: 236 kg (single bearing) / 224 kg (double bearing)

  • Packing Dimensions: 84 × 59 × 75 cm

Regulation & Control

  • Excitation: Self-excited, AVR-controlled

  • AVR Model: SX460 (standard), SX440 optional

  • Voltage Regulation Accuracy: ±1.0%

  • Parallel Operation: Supported (AVR-dependent)

  • RFI Suppression: BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N compliant

  • Standards Compliance: IEC60034, GB755, BS5000, VDE0530, NEMA MG1-22, CSA C22.2-100, AS1359

  • Certification: ISO9001 Quality Management System

Environmental Parameters

  • Operating Temperature: –15°C to +40°C

  • Relative Humidity: Up to 95% (non-condensing)

  • Altitude: Up to 1000 m without derating

  • Cooling Air Requirement: 0.15–0.19 m³/s depending on frequency

  • Noise & Vibration: Balanced per BS6861 mechanical standards

Performance Summary

  • Efficiency Range: 86.7–87.8%

  • Voltage Dip (Transient Load): ≤25% at 0.8 PF

  • Recovery Time: <0.5 seconds

  • Locked Rotor Motor Starting: >300% rated current

  • Applications: Prime power, standby, rental, telecom, mobile, lighting tower, refrigeration, and railway generator systems

Datasheet