Type: Three-phase, brushless, self-excited synchronous alternator with PMG excitation
-
Frequency: 50 / 60 Hz
-
Power Factor: 0.8
-
Voltage Range: 380/220V – 480/277V (reconnectable in star, delta, or parallel star)
-
Voltage Regulation: ±1.0%
-
Total Harmonic Distortion (THD): <5% (balanced linear load), <1.5% (no-load)
-
Sustained Short Circuit Current: >300% rated current for 10 seconds
-
Efficiency: Up to 96.1%
-
Overload Capacity: 110% for one hour in a six-hour period
-
Telephone Harmonic Factor (THF): <2%
-
Telephone Interference Factor (TIF): <50
-
Short Circuit Ratio (1/Xd): 0.20
-
Reactances (Per Unit at Rated kVA):
-
Xd (Synchronous): 2.28–3.28
-
X’d (Transient): 0.18–0.21
-
X’’d (Subtransient): 0.17–0.19
-
Xq (Quadrature): 2.05–3.17
-
X’’q (Quadrature Subtransient): 0.22–0.27
-
X₂ (Negative Sequence): 0.14–0.16
-
X₀ (Zero Sequence): 0.04–0.05
-
Leakage Reactance (XL): 0.03–0.04
-
Time Constants:
-
Voltage Regulation Accuracy: ±1.0%
-
Voltage Waveform: <1.5% THD (no-load), <5.0% THD (linear load)
-
Insulation Class: H (125°C rise at 40°C ambient)
-
Protection: IP23 (optional IP44 with 5–10% power reduction)
-
Cooling: Self-ventilated air cooling system
-
Frame: Rigid steel structure with cast aluminum front and rear covers
-
Stator: Double-layer winding with 2/3 pitch design eliminating triple harmonics
-
Rotor: Damped rotor dynamically balanced per BS6861 standards
-
Bearings:
-
Drive End: 6319 (ISO, sealed-for-life ball bearing)
-
Non-Drive End: 6228 (ISO, sealed-for-life ball bearing)
-
Overspeed Capability: 120% of rated speed (2250 rpm)
-
Leads: 12 reconnectable leads for star, delta, or parallel star configuration
-
Inertia (WR²): 32.0076–33.0084 kg·m²
-
Cooling Air Requirement: 2.64 m³/s (50Hz), 3.17 m³/s (60Hz)
-
Winding Resistance:
-
Excitation System: PMG excitation with brushless AVR
-
AVR Models: MX321 (standard), optional MX341, SX440, SX460, AS440
-
Voltage Regulation Accuracy: ±1.0%
-
Parallel Operation: Supported (AVR-dependent)
-
Protection Features:
-
Stator winding and bearing overheat protection
-
Anti-condensation heater (optional)
-
Low-speed voltage drop protection
-
RFI Suppression: Complies with BS EN 61000-6-2 & BS EN 61000-6-4, VDE 0875G/N
-
Standards Compliance: IEC60034, GB755, BS5000, NEMA MG1-22, CSA C22.2-100, AS1359
-
Certification: ISO9001 Quality Management System